DNDS errors

Potential errors could be

1) LEDs to both sides (left and right) of the in- and output module do not light up 

Reason: No measuring system

                Sensor error at IN1 or IN2 or at both of them

 

2) LEDs to both sides (left and right) of the output module do not light up 

Reason:    E1 or E2 or both oft hem are not connected to 24V

 

3) LEDs to both sides (left and right) of the output module briefly flash green

Reason:   one of the contacts does not close or open

                  Time setting is not the same in both channels

 

4) LED on the left or right of the input module flashes at 1Hz 

Reason:    Track A or B of the measuring system is missing

 

5) The right LED goes out at a standstill.

Reason:    Saving of previous V > Vmax.

                  -> Acknowledgment by 2 sec. Power off

 

6) LED on the left or right of the input module flashes at 2Hz

Reason:   DNDS malfunction or malfunction due to improperly laid signal lines.

                   ->  Acknowledgment by 2 sec. Power off